Description
Compound inslation with EPDM rubber, EPDM jacket, Fluoropolymer tape
and Fibre tape covered completely over the jacket, Full galvanized steel
(or stainless steel or Monel)tape armour.
Performing Criterion
GB1T16750-1997 J35332-91
Application Range
This cable is applicable for use in Electricity Submersible Pump Units with rated voltage less than 4kV or 5kV. The
permissible working temperature is 205"C(40O0F). The cable has the excellent ability of oil-resistance and .
corrosion-resistance.
Cable's Cross Section Chart
Specification and Parameters
|
Phase
|
Cross Section mm sq
|
Conductor Diameter mm
|
DC Resistance at 20°C ≤ Ω/ km
|
Insulation Thickness mm
|
Jacket Thickness mm
|
Overall Size and Weight
|
|
4kV
|
5kV
|
|
Not tinned
|
Tinned
|
4kV
|
5kV
|
mm
|
kg/km
|
mm
|
kg/km
|
|
3
|
16
|
1/4.62
|
1.15
|
1.16
|
2.0
|
2.3
|
2.0
|
27
|
1500
|
29
|
1700
|
|
3
|
20
|
1/5.19
|
0.84
|
0.86
|
2.0
|
2.3
|
2.0
|
28
|
1700
|
31
|
1900
|
|
3
|
33
|
1/6.54
|
0.54
|
0.56
|
2.0
|
2.3
|
2.0
|
32
|
2230
|
34
|
2430
|
|
3
|
42
|
1/7.35
|
0.43
|
0.44
|
2.0
|
2.3
|
2.0
|
34
|
2666
|
37
|
2850
|
Index of Performance
|
Cross Section
|
Conductor Diameter mm
|
4kV Insulation Resistance MΩ.km
|
4kV Leakage Current at 15.6 μA/km/kV
|
5kV Insulation Resistance MΩ.km
|
5kV Leakage Current at 15.6 μA/km/kV
|
DC Voltage Test For 5 Minutes
|
|
4kV
|
5kV
|
|
16
|
4.62
|
1484
|
0.7
|
1692
|
0.607
|
27
|
35
|
|
20 AWG4
|
5.19
|
1352
|
0.775
|
1548
|
0.656
|
|
33 AWG2
|
6.54
|
1012
|
0.984
|
1170
|
0.853
|
|
42 AWG1
|
7.35
|
919
|
1.083
|
1063
|
0.951
|
|